TEMPCO Electric Heater Corporation
Instrumentation

Home | Product Lines | Instrumentation Hub | Temperature Transmitters Hub

2-Wire Panel Rail Mount Universal Temperature/Process Transmitters

Input and Output Connection Drawings | Specifications | How to Order

Temperature transmitters are used for a variety of reasons. The use of temperature transmitters can eliminate the need for long costly runs of thermocouple wire vs. less expensive copper signal wire. When the environment is electrically noisy, sending a 4-20 mA signal to the control room reduces the chance of error.
The Tempco ETR Series of 2-wire transmitters offers both isolated and non-isolated versions. They are designed to fit directly on a standard 35mm DIN Rail.
 
Programmable in the field with your PC
and easy-to-use software!!!


Available From Stock!
 Design Features
  • Accepts T/C and 2- or 3-wire RTD sensors
  • Field programmable with easy to use MS Windows®-based configuration software and a PC
  • Consistent sensor break function
  • Current loop test function
  • Full access to all features while in operation
  • Temperature linear output
  • NAMUR-compliant
  • Configuration, editing & reading without external power
  • Easy wiring with a large center hole
 Additional Design Features for Isolated Version:
  • Fully universal, linearized and isolated 3/4 wire RTD, T/C, mV and Ohm
  • Sensor and system error correction
  • Low sensor isolation detection
  • Simplified loop check up with calibration output
     
The ETR Transmitters are built using surface mount components and employ digital technology with non- volatile memory to retain the configuration after programming and the cable is removed.

Input Connections - Common to both miniature & panel mount Panel Rail Mount Transmitter Output Connections
Pt100 2 or 3 wire Thermocouple

Additional inputs for the Isolated Version
Pt100 4 wire Thermocouple / mV Potentiometer 3-wire

Specifications

Non-Isolated Isolated
Isolation: --- 1500 VAC
Input-RTD (PT100 or D100): 2 or 3 wire 3 or 4 wire
• TC: AE, B, E, J, K, L, N, R, S, T, U
• Potentiometer/resistance: --- 0 to 2000 Ω
• Voltage: --- -10 to 500 mVDC
Sensor current: ~ 0.4 mA
Max. sensor: RTD: 25 Ω per wire
Wire resistance: T/C: 500 Ω (total loop)
Sensor Failure: Updscale, Downscale or Off
Adjustments - Zero: Any value within range limits
Adjustments-Span: RTD: 18°F/10°C 18°F/10°C
T/C: 2 mV 2 mV
Resistance: --- 10 Ω
Cold Junction Compensation T/C: ±0.9°F / ±0.5°C
Supply Voltage: 8 to 36 Vdc 6.5 to 36 Vdc
Operating Temperature: -40° to  +185°F/-40° to +70°C
Humidity: 0 to 95% non-condensing
Typical Accuracy: ±0.2% of span ±0.1% of span
Common Panel Rail Mount
Temperature Transmitters
Part No. Isolation Input Range Unit
zero span
ETR20101 no K tc 0 200 °F
ETR20102 no J tc 0 200 °F
ETR20103 yes RTD 0 200 °F
ETR20104 no K tc 0 500 °F
ETR20105 no J tc 0 500 °F
ETR20106 yes RTD 0 400 °F
ETR20107 no K tc 0 200 °C
ETR20108 no J tc 0 200 °C
ETR20109 no K tc 0 400 °C
ETR20110 no J tc 0 400 °C

Un-Programmed Miniature Transmitters
ETR20001 For Non-Isolated version
ETR20002 For Isolated version

Programming Software
(Includes RS232 interface cable)
ETR90003 For Non-Isolated version
ETR90004 For Isolated version


How To Order
Create an ordering code by filling in the boxes with the appropriate number and/or letter designation for your requirements and a part number will be assigned, or choose a pre-assigned configuration.

Available From Stock!